[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933916":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933916,604,1,"单选题","变电站的地上层与地下室共用楼梯间时，应在地上首层采用耐火极限不低于2h的不燃烧体隔墙和（ ）级防火门将地下或半地下部分与地上部分的连通部分完全隔开，并应有明显标志。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","甲",false,{"key":16,"text":17,"correct":18},"B","乙",true,{"key":20,"text":21,"correct":14},"C","丙",{"key":23,"text":24,"correct":14},"D","丁","地下变电站安全出口数量不应少于2个。地下室与地上层不应共用楼梯间，当必须共用楼梯间时，应在地上首层采用耐火极限不低于2h的不燃烧体隔墙和乙级防火门将地下或半地下部分与地上部分的连通部分完全隔开，并应有明显标志。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]