[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933775":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},933775,604,1,"单选题","甲、乙类可燃气体的高大构架和设备群应设置水炮保护，其设置位置距保护对象不宜小于（ ）m。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","15",true,{"key":16,"text":17,"correct":18},"B","30",false,{"key":20,"text":21,"correct":18},"C","50",{"key":23,"text":24,"correct":18},"D","60","根据《石油化工企业设计防火规范》GB 50160—2008 8.6.1 甲、乙类可燃气体，可燃液体设备的高大构架和设备群应设置水炮保护，其设置位置距保护对象不宜小于15m。 8.6.2 固定式水炮的布置应根据水炮的设计流量和有效射程确定其保护范围。消防水炮距被保护对象不宜小于15m。消防水炮的出水量宜为30~50L\u002Fs，水炮应具有直流和水雾两种喷射方式。 本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]