[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933766":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933766,604,2,"多选题","某居民住宅楼，地上20层，地下1层，建筑高度58m，采用临时高压消防给水系统，屋顶设置消防水箱。下列关于消防水箱设置的说法中，正确的是（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","水箱的有效容积不应小于12m3",false,{"key":16,"text":17,"correct":18},"B","水箱的有效容积不应小于18m3",true,{"key":20,"text":21,"correct":14},"C","水箱的最低有效水位应满足最不利点处的静水压力不低于0．1MPa",{"key":23,"text":24,"correct":14},"D","水箱的最低有效水位应满足最不利点处的静水压力不低于0．15MPa",{"key":26,"text":27,"correct":18},"E","水箱的最低有效水位应满足最不利点处的静水压力不低于0．07MPa","BE","根据《消防给水及消火栓系统技术规范》（GB50974-2014）第5．2．1条规定，临时高压消防给水系统的高位消防水箱的有效容积应满足初期火灾消防用水量的要求，一类高层住宅不应小于18m3，故选B，不选A。 根据该规范第5．2．2条规定，高位消防水箱的设置位置应高于其所服务的水灭火设施，且最低有效水位应满足水灭火设施最不利点处的静水压力，高层住宅不应低于0．07MPa，故选E，不选C、D。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]