[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933765":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933765,604,2,"多选题","下列哪些建筑物应设消防水池（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","市政给水管网两路供水，并采用两条引入管，室外消火栓设计流量为25L\u002Fs",false,{"key":16,"text":17,"correct":18},"B","市政给水管网一路供水，室外消火栓设计流量为25L\u002Fs",true,{"key":20,"text":21,"correct":18},"C","市政给水管网一路供水，室外消火栓设计流量为15L\u002Fs，建筑高度为60m",{"key":23,"text":24,"correct":18},"D","市政消防给水设计流量小于建筑的消防给水设计流量时",{"key":26,"text":27,"correct":18},"E","生产、生活用水量达到最大时，市政给水管网不能满足室内、外消防用水量","BCDE","根据《消防给水及消火栓系统技术规范》（GB50974-2014）中第4.3.1条规定，符合下列规定之一时，应设置消防水池： （1）当生产、生活用水量达到最大时，市政给水管网或引入管不能满足室内、外消防用水量时；因此E正确。 （2）当采用一路消防供水或只有一条引入管，且室外消火栓设计流量大于20L\u002Fs或建筑高度大于50m时；因此BC正确。 （3）市政消防给水设计流量小于建筑的消防给水设计流量时。因此D正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]