[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933764":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933764,604,2,"多选题","下列建筑应设室内消火栓系统的是（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","建筑占地面积大于300m2的厂房（仓库）",true,{"key":16,"text":17,"correct":14},"B","体积大于5000m3的车站、码头、机场的候车（船、机）楼以及展览建筑、商店、旅馆、病房楼、门诊楼、图书馆等",{"key":19,"text":20,"correct":14},"C","建筑高度大于15m或体积大于10000m3的办公楼、教学楼",{"key":22,"text":23,"correct":24},"D","耐火等级为三、四级且建筑体积小于等于5000m3的戊类厂房（仓库）",false,{"key":26,"text":27,"correct":14},"E","建筑高度大于21m的住宅","ABCE","下列建筑应设室内消火栓系统：（1）建筑占地面积大于300m2的厂房（仓库）。（2）体积大于5000m3的车站、码头、机场的候车（船、机）楼以及展览建筑、商店建筑、旅馆建筑、医疗建筑、图书馆建筑等单层、多层建筑。（3）特等、甲等剧场，超过800个座位的其他等级的剧场和电影院等，超过1200个座位的礼堂、体育馆等单层、多层建筑。（4）建筑高度大于15m或体积大于10000m3的办公建筑、教学建筑和其他单层、多层民用建筑。（5）高层公共建筑和建筑高度大于21m的住宅建筑。（6）对于建筑高度不大于27m的住宅建筑，当确有困难时，可只设置干式消防竖管和不带消火栓箱的DN65的室内消火栓。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]