[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933761":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933761,604,2,"多选题","某一级耐火等级多层丙类仓库，建筑总体积5000m3，建筑高度24m，设有室内消火栓系统。下列关于该系统设置的做法，错误的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","该仓库消火栓栓口动压为0．20MPa",true,{"key":16,"text":17,"correct":18},"B","该仓库内消火栓的布置间距为50m",false,{"key":20,"text":21,"correct":14},"C","配备长度为30m的消防水带",{"key":23,"text":24,"correct":18},"D","采用DN65的室内消火栓",{"key":26,"text":27,"correct":14},"E","消防水枪充实水柱为7m","ACE","根据《消防给水及消火栓系统技术规范》GB50974—20147．4．12—2，高层建筑、厂房、库房和室内净空高度超过8m的民用建筑等场所，消火栓栓口动压不应小于0．35MPa，且消防水枪充实水柱应按13m计算；其他场所，消火栓栓口动压不应小于0．25MPa，且消防水枪充实水柱应按10m计算，AE选项错误；根据7．4．6，室内消火栓的布置应满足同一平面有2支消防水枪的2股充实水柱同时达到任何部位的要求，但建筑高度小于或等于24．0m且体积小于或等于5000m3的多层仓库、建筑高度小于或等于54m且每单元设置一部疏散楼梯的住宅，以及本规范表3．5．2，中规定可采用1支消防水枪的场所，可采用1支消防水枪的1股充实水柱到达室内任何部位；根据7．4．10—2，室内消火栓宜按直线距离计算其布置间距：消火栓按1支消防水枪的1股充实水柱布置的建筑物，消火栓的布置间距不应大于50．0m，B选项正确；根据7．4．2—1，应采用DN65室内消火栓，并可与消防软管卷盘或轻便水龙设置在同一箱体内；根据7．4．2—2。应配置公称直径65有内衬里的消防水带，长度不宜超过25．0m，C选项错误，D选项正确。本题答案为ACE。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]