[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933758":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933758,604,1,"单选题","某商业建筑，东西长100m，南北宽60m，建筑高度26m，室外消火栓设计流量为40L／s，南侧布置消防扑救面。沿该建筑南侧消防扑救面设置的室外消火栓数量，不宜少于（ ）个。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1",false,{"key":16,"text":17,"correct":18},"B","2",true,{"key":20,"text":21,"correct":14},"C","3",{"key":23,"text":24,"correct":14},"D","4","根据《消防给水及消火栓系统技术规范》（GB50974—2014）第7．3．2条规定，建筑室外消火栓的数量应根据室外消火栓设计流量和保护半径经计算确定，保护半径不应大于150．0m，每个室外消火栓的出流量宜按10～15L／s计算。则该商业建筑室外消火栓个数不应小于40／15≈3（个）。根据第7．3．3条规定，室外消火栓宜沿建筑周围均匀布置，且不宜集中布置在建筑一侧；建筑消防扑救面一侧的室外消火栓数量不宜少于2个。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]