[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933756":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933756,604,1,"单选题","下列关于分区供水应符合条件的说法，错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","系统的工作压力大于2．4MPa",false,{"key":16,"text":17,"correct":14},"B","消火栓栓口处静压大于1．0MPa",{"key":19,"text":20,"correct":21},"C","自动水灭火系统报警阀处的工作压力大于1．50MPa",true,{"key":23,"text":24,"correct":14},"D","自动水灭火系统喷头处的工作压力大于1．20MPa","根据《消防给水及消火栓系统技术规范》GB50974—20146．2．1，符合下列条件时，消防给水系统应分区供水： 1）系统工作压力大于2．40MPa。 2）消火栓栓口处静压大于1．0MPa。 3）自动水灭火系统报警阀处的工作压力大于1．60MPa或喷头处的工作压力大于1．20MPa。 本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]