[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933752":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933752,604,1,"单选题","关于室内消防给水管道设置的说法，错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","室内消火栓竖管管径不应小于DN100",false,{"key":16,"text":17,"correct":14},"B","每根竖管与供水横干管相接处应设置阀门",{"key":19,"text":20,"correct":21},"C","当室外消火栓设计流量不大于20L／s，且室内消火栓不超过10个时，室内消火栓系统管网应布置成环状",true,{"key":23,"text":24,"correct":14},"D","合用消防泵时，供水管路沿水流方向应在报警阀前分开设置","室内消火栓系统管网应布置成环状，当室外消火栓设计流量不大于 20 L\u002Fs，且室内消火栓不超过 10 个时，除《消防给水及消火栓系统技术规范》（ GB 50974-2014 ）第 8. 1. 2条外，可布置成枝状。C选项错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]