[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933749":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933749,604,1,"单选题","下列关于室内消火栓设置要求的说法，错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","消火栓按2支消防水枪的2股充实水柱布置的建筑物，消火栓的布置间距不应大于30．0m",false,{"key":16,"text":17,"correct":14},"B","消火栓按1支消防水枪的1股充实水柱布置的建筑物，消火栓的布置间距不应大于50．0m",{"key":19,"text":20,"correct":14},"C","设有室内消火栓的建筑应设置带有压力表的试验消火栓",{"key":22,"text":23,"correct":24},"D","消防电梯前室应设置室内消火栓，该消火栓不应计入消火栓使用数量",true,"根据《消防给水及消火栓系统技术规范》GB50974—20147．4．10，室内消火栓宜按直线距离计算其布置间距，并应符合下列规定：1）消火栓按2支消防水枪的2股充实水柱布置的建筑物，消火栓的布置间距不应大于30．0m，A选项正确；2）消火栓按1支消防水枪的1股充实水柱布置的建筑物，消火栓的布置间距不应大于50．0m，B选项正确；根据7．4．9，设有室内消火栓的建筑应设置带有压力表的试验消火栓，C选项正确；根据7．4．5，消防电梯前室应设置室内消火栓，并应计入消火栓使用数量，D选项错误。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]