[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933741":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933741,604,1,"单选题","某高层综合楼，室内、外消火栓的设计流量均为20L／s，自动喷水灭火系统的设计流量为15L／s。市政给水管网能够保证室外消防用水，消防水池储存室内消火栓和自动喷水灭火系统的用水量，消防水池有符合要求的补水措施，两路补水量均为30m3／h。该建筑消防水池的最小有效容积为（ ）m3。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","104",false,{"key":16,"text":17,"correct":18},"B","180",true,{"key":20,"text":21,"correct":14},"C","240",{"key":23,"text":24,"correct":14},"D","270","根据《消防给水及消火栓系统技术规范》GB50974—2014表3．6．2，高层综合楼消火栓系统的火灾延续时间不应低于3h；自动喷水灭火系统的火灾延续时间为1h。消防水池储存室内消火栓和自动喷水灭火系统的用水量，建筑室内消防用水量应为20×3×3．6+15×1×3．6=270m3;消防水池在火灾延续时间内的连续补水量为30×3=90m3，所以建筑消防水池最小有效容积应为270-90=180m3。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]