[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933740":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933740,604,1,"单选题","高位消防水箱的最低有效水位应根据出水管喇叭口和防止旋流器的淹没深度确定，当采用防止旋流器时最低有效水位的保护高度不应小于（ ）mm。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","50",false,{"key":16,"text":17,"correct":14},"B","100",{"key":19,"text":20,"correct":21},"C","150",true,{"key":23,"text":24,"correct":14},"D","200","《消防给水及消火栓系统技术规范》GB50974-2014中5.2.6. 2条：高位消防水箱最低有效水位应依据出水管喇叭口和防止旋流器的淹没深度确定，当采用喇叭口时，应符合本规范地5.1.3条第四款的规定；当采用防止旋流器时应根据产品确定，且不应小于150mm的保护高度。 5.1.13 离心式消防水泵吸水管、出水管和阀门等,应符合下列规定： 消防水泵吸水口的淹没深度应满足消防水泵在最低水位运行安全的要求,吸水管喇叭口在消防水池最低有效水位下的淹没深度应根据吸水管喇叭口的水流速度和水力条件确定,但不应小于600mm。当釆用旋流防止器时,淹没深度不应小于200mm; 本题为“高位消防水箱的最低有效水位”应该选择150mm。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]