[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933739":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},933739,604,1,"单选题","下列关于消防水泵接合器设置要求的说法，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","墙壁消防水泵接合器的安装高度距地面宜为1．10m",true,{"key":16,"text":17,"correct":18},"B","水泵接合器处应设置永久性标志铭牌，并应标明供水系统、供水范围和额定压力",false,{"key":20,"text":21,"correct":18},"C","墙壁消防水泵接合器与墙面上的门、窗、孔、洞的净距离不应小于2m，且不应安装在玻璃幕墙下方",{"key":23,"text":24,"correct":18},"D","水泵接合器应设在室外便于消防车使用的地点","根据《消防给水及消火栓系统技术规范》GB50974—20145．4．8，墙壁消防水泵接合器的安装高度距地面宜为0．70m；与墙面上的门、窗、孔、洞的净距离不应小于2．0m，且不应安装在玻璃幕墙下方； 根据5．4．9，水泵接合器处应设置永久性标志铭牌，并应标明供水系统、供水范围和额定压力； 根据5．4．7，水泵接合器应设在室外便于消防车使用的地点，且距室外消火栓或消防水池的距离不宜小于15m，并不宜大于40m。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]