[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933734":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933734,604,1,"单选题","消防水泵的供电应符合现行国家标准《供配电系统设计规范》（GB50052--2009）的要求，消防水泵双电源切换时，一路电源与柴油发电机的切换时间不应大于（ ）s。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","2",false,{"key":16,"text":17,"correct":14},"B","5",{"key":19,"text":20,"correct":14},"C","10",{"key":22,"text":23,"correct":24},"D","15",true,"根据《消防给水及消火栓系统技术规范》GB50974—201411．0．17，消防水泵的双电源切换应符合下列规定：双路电源自动切换时间不应大于2s；当一路电源与内燃机动力的切换时间不应大于15s。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]