[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933731":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933731,604,1,"单选题","某采用临时高压消防给水系统的建筑设有两台消防水泵，设计流量分别为15L／s和30L／s，则该建筑在选用备用泵时流量不应低于（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","10L／s",false,{"key":16,"text":17,"correct":18},"B","30L／s",true,{"key":20,"text":21,"correct":14},"C","15L／s",{"key":23,"text":24,"correct":14},"D","25L／s","根据《消防给水及消火栓系统技术规范》GB50974—20145．1．10，消防水泵应设置备用泵，其性能应与工作泵性能一致。备用泵的工作能力不应小于最大一台消防工作泵的工作能力，以保证任何一台工作泵发生故障或需进行维修时备用泵投入后的总工作能力不会降低。根据题意，最大一台工作泵的用水量为30L／s。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]