[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933728":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933728,604,2,"多选题","下列关于串联分区供水的说法，正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","转输水箱可以兼做高位水箱，有效储水容积不应小于 60m3",true,{"key":16,"text":17,"correct":18},"B","串联分区宜采用直接串联的方式",false,{"key":20,"text":21,"correct":14},"C","直接串联时，应先启动低区消防水泵，再启动高区消防水泵",{"key":23,"text":24,"correct":18},"D","采用转输水箱间接串联时，应先启动转输泵，再启动高区泵",{"key":26,"text":27,"correct":14},"E","转输水箱的溢流管宜接至消防水池","ACE","此题考查的是串联分区供水，注意和并联的区别 1）采用消防水泵串联分区供水时，宜采用消防水泵转输水箱串联供水方式，并符合下列规定: ①当采用消防水泵转输水箱串联时，转输水箱的有效储水容积不应小于 60m3 ，转输水箱可作为高位消防水箱 。 ②串联转输水箱的溢流管宜连接到消防水池。 ③当采用消防水泵直接串联时，应采取确保供水可靠性的措施，且消防水泵从低区到高区应能依次顺序启动。 ④当采用消防水泵直接串联时，应校核系统供水压力，并应在串联消防水泵出水管上设置减压型倒流防止器。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]