[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933726":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933726,604,2,"多选题","下列（ ）场所的消火栓系统应设置水泵接合器。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","高层民用建筑",true,{"key":16,"text":17,"correct":18},"B","地下两层的公共建筑",false,{"key":20,"text":21,"correct":14},"C","高层工业建筑",{"key":23,"text":24,"correct":18},"D","四层的多层工业建筑",{"key":26,"text":27,"correct":18},"E","四层的多层公共建筑","AC","本题考查的是水泵接合器的设置要求 高层民用建筑、设有消防给水的住宅、超过五层的其他多层民用建筑、超过两层或建筑面积大于 10000平米的地下或半地下建筑（室）、室内消火栓设计流量大于 10 L\u002Fs， 平战结合的人防工程、高层工业建筑和超过四层的多层工业建筑、城市交通隧道，其室内消火栓给水系统应设水泵接合器;自动喷水灭火系统、水喷雾灭火系统、泡沫灭火系统和固定消防炮灭火系统 等水灭火系统，均应设置消防水泵接合器。 故本题答案为AC",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]