[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933724":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933724,604,2,"多选题","根据《消防给水及消火栓系统技术规范》GB50974—2014，关于消防水泵房设计规定，下列说法不正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","寒冷地区无人值守的消防水泵房采暖温度不应低于3℃",true,{"key":16,"text":17,"correct":18},"B","消防水泵房的通风宜按6次／h设计",false,{"key":20,"text":21,"correct":14},"C","附设在建筑物内的消防水泵房，开向疏散走道的门应采用乙级防火门",{"key":23,"text":24,"correct":18},"D","消防水泵房应设置排水设施",{"key":26,"text":27,"correct":14},"E","附设在建筑物内的消防水泵房，不应设置在地下二层及以下楼层","ACE","根据《消防给水及消火栓系统技术规范》GB50974—20145．5．9，消防水泵房的设计应根据具体情况设计相应的采暖、通风和排水设施，并应符合下列规定：严寒、寒冷等冬季结冰地区采暖温度不应低于10℃，但当无人值守时不应低于5℃；消防水泵房的通风宜按6次／h设计；消防水泵房应设置排水设施，A选项错误，BD选项正确；根据5．5．12—3，附设在建筑物内的消防水泵房，应采用耐火极限不低于2．0h的隔墙和1．50h的楼板与其他部位隔开，其疏散门应直通安全出口，且开向疏散走道的门应采用甲级防火门，C选项错误；根据5．5．12—2，附设在建筑物内的消防水泵房，不应设置在地下三层及以下，或室内地面与室外出入口地坪高差大于10m的地下楼层，E选项错误。本题答案为ACE。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]