[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933711":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933711,604,1,"单选题","某高层公共建筑，设置由高位消防水箱稳压的临时高压系统，消防水泵和消防水池均设在地下一层，高位消防水箱最低水位与最不利点消火栓的高差为 8m，与地下室消火栓高差为 42m，消防水泵吸水口与消防水池最高水位之间的高差为 2m，消防水泵零流量时扬程为 120m，该给水系统工作压力为（ ）MPa。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1.2",false,{"key":16,"text":17,"correct":18},"B","1.22",true,{"key":20,"text":21,"correct":14},"C","1.62",{"key":23,"text":24,"correct":14},"D","1.28","本题考查的是给水系统的工作压力。采用高位消防水箱稳压的临时高压消防给水系统的工作压力应为消防水泵零流量时压力与与水泵吸水口最大静水压力之和。系统工作压力=水泵零流量时压力+水泵吸水口最大静水压力=120\u002F100+2\u002F100=1.20+0.02=1.22；所以，本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]