[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933708":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933708,604,1,"单选题","下列关于消防水泵的说法中错误的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","当采用离心泵时，水泵启动时其叶轮必须浸没在水中",false,{"key":16,"text":17,"correct":14},"B","为保证消防水泵及时、可靠地启动，吸水管应采用自灌式吸水",{"key":19,"text":20,"correct":21},"C","消防水泵的吸水管变径时，可采用同心异径管",true,{"key":23,"text":24,"correct":14},"D","消防水泵吸水口的淹没深度应满足消防水泵在最低水位运行安全的要求","根据离心泵的特性，启动时水泵叶轮必须浸没在水中。为保证消防泵及时、可靠地启动，吸水管应采用自灌式吸水，在自灌方式吸水时，吸水管上应装设阀门，以便于检修，AB选项正确；根据《消防给水及消火栓系统技术规范》GB50974—20145．1．13—2，消防水泵吸水管布置应避免形成气囊，变径时，可采用偏心异径管，并采用管顶平接，C选项错误；根据5．1．13—4，消防水泵吸水口的淹没深度应满足消防水泵在最低水位运行安全的要求，吸水管喇叭口在消防水池最低有效水位下的淹没深度应根据吸水管喇叭口的水流速度和水力条件确定，但不应小于600mm。当采用旋流防止器时，淹没深度不应小于200mm，D选项正确。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]