[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933702":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933702,604,1,"单选题","下列关于可以不设置备用消防水泵的说法中，错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","建筑高度为40米的住宅",false,{"key":16,"text":17,"correct":14},"B","室内消防给水设计流量为10L／s的宿舍楼",{"key":19,"text":20,"correct":21},"C","室外消防给水设计流量为30L／s的玻璃厂房",true,{"key":23,"text":24,"correct":14},"D","室内消防给水设计流量为10L／s的甲醇生产厂房","根据现行国家标准《消防给水及消火栓系统技术规范》（GB50974—2014）的规定，下列情况下可不设备用泵。 1）建筑高度小于54m的住宅和室外消防给水设计流量小于或等于25L／s时。 2）建筑的室内消防给水设计流量小于或等于10L／s的建筑。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]