[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933701":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933701,604,1,"单选题","高层建筑、厂房、库房和室内净空高度超过8m的民用建筑等场所，其消火栓栓口动压不应小于0．35MPa，且消防水枪充实水柱应达到（ ）m。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","8",false,{"key":16,"text":17,"correct":14},"B","12",{"key":19,"text":20,"correct":21},"C","13",true,{"key":23,"text":24,"correct":14},"D","16","根据《消防给水及消火栓系统技术规范》GB 50974-2014中7.4.12-2，高层建筑、厂房、库房和室内净空高度超过8m的民用建筑等场所，消火栓栓口动压不应小于0.35MPa，且消防水枪充实水柱应按13m计算；其他场所，消火栓栓口动压不应小于0.25MPa，且消防水枪充实水柱应按10m计算。 因此本题选C",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]