[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933700":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933700,604,1,"单选题","甲、乙、丙类液体储罐区和液化石油气储罐区的消火栓应设置在防火堤或防护墙外，距罐壁（ ）m范围内的消火栓，不应计算在该罐可使用的数量内。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","8",false,{"key":16,"text":17,"correct":14},"B","10",{"key":19,"text":20,"correct":21},"C","15",true,{"key":23,"text":24,"correct":14},"D","18","根据《消防给水及消火栓系统技术规范》GB 50974-2014中7．3．6，甲、乙、丙类液体和液化石油气等罐区发生火灾，火场温度高，人员很难接近，同时还有可能发生泄漏和爆炸。因此，要求室外消火栓设置在防火堤或防护墙外的安全地点。距罐壁15m范围内的室外消火栓火灾发生时因辐射热而难以使用，故不应计算在该罐可使用的数量内。因此本题选择C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]