[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933693":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933693,604,1,"单选题","当室外消防给水系统因引入管设有倒流防止器，在火灾时因其水头损失导致室外消火栓的出流量和压力不能满足相应的要求时，应采取的有效措施是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","增加供水时间",false,{"key":16,"text":17,"correct":14},"B","采用高压消防给水系统",{"key":19,"text":20,"correct":14},"C","在倒流防止器后增加室外消火栓",{"key":22,"text":23,"correct":24},"D","在倒流防止器前增加室外消火栓",true,"根据《消防给水及消火栓系统技术规范》GB50974—20147．3．10，室外消防给水引入管当设有倒流防止器，且火灾时因其水头损失导致室外消火栓不能满足本规范第7．2．8条的要求时，应在该倒流防止器前设置一个室外消火栓。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]