[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933692":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933692,604,1,"单选题","下列有关消防水泵吸水管和出水管上设置压力表的说法，不正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","压力表应采用直径不小于6mm的管道与消防水泵进出口管相接",false,{"key":16,"text":17,"correct":14},"B","压力表的直径不应小于100mm",{"key":19,"text":20,"correct":21},"C","消防水泵出水管压力表的最大量程不应低于设计工作压力的3倍，且不应低于1．6MPa",true,{"key":23,"text":24,"correct":14},"D","消防水泵吸水管上压力表的最大量程不应低于0．7MPa","根据《消防给水及消火栓系统技术规范》GB50974—20145．1．17，消防水泵吸水管和出水管上应设置压力表，并应符合下列规定： 1）消防水泵出水管压力表的最大量程不应低于其设计工作压力的2倍，且不应低于1．60MPa。 2）消防水泵吸水管宜设置真空表、压力表或真空压力表，压力表的最大量程应根据工程具体情况确定，但不应低于0．70MPa，真空表的最大量程宜为-0．10MPa。 3）压力表的直径不应小于100mm，应采用直径不小于6mm的管道与消防水泵进出口管相接，并应设置关断阀门。 本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]