[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933690":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933690,604,1,"单选题","室内消火栓栓口静压大于（ ）MPa时应采取分区供水。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","0．35",false,{"key":16,"text":17,"correct":14},"B","0．5",{"key":19,"text":20,"correct":14},"C","0．7",{"key":22,"text":23,"correct":24},"D","1．0",true,"根据《消防给水及消火栓系统技术规范》GB50974—20146．2．1，符合下列条件时，消防给水系统应分区供水： 1）系统工作压力大于2．40MPa。 2）消火栓栓口处静压大于1．0MPa。 3）自动水灭火系统报警阀处的工作压力大于1．60MPa或喷头处的工作压力大于1．20MPa。 本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]