[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933687":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933687,604,1,"单选题","某建筑高度为62m的办公楼，地上12层，采用临时高压消防给水形式，设有室内外消火栓系统，当系统工作压力为3．2MPa时，应采用（ ）方式减压。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","减压阀",false,{"key":16,"text":17,"correct":18},"B","消防水泵串联",true,{"key":20,"text":21,"correct":14},"C","节流管",{"key":23,"text":24,"correct":14},"D","减压孔板","根据《消防给水及消火栓系统技术规范》GB50974—20146．2．2，分区供水形式应根据系统压力、建筑特征，经技术经济和安全可靠性等综合因素确定，可采用消防水泵并行或串联、减压水箱和减压阀减压的形式，但当系统的工作压力大于2．40MPa时，应采用消防水泵串联或减压水箱分区供水形式。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]