[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933686":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},933686,604,1,"单选题","某采用临时高压消防给水系统的工艺装置区周围设有室外消火栓，根据《消防给水及消火栓系统技术规范》（GB50974—2014）的规定，其间距不应大于（ ）m。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","60",true,{"key":16,"text":17,"correct":18},"B","80",false,{"key":20,"text":21,"correct":18},"C","120",{"key":23,"text":24,"correct":18},"D","150","根据《消防给水及消火栓系统技术规范》GB50974—20147．3．7，工艺装置区等采用高压或临时高压消防给水系统的场所，其周围应设置室外消火栓，数量应根据设计流量经计算确定，且间距不应大于60．0m。当工艺装置区宽度大于120．0m时，宜在该装置区内的路边设置室外消火栓。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]