[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933682":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933682,604,1,"单选题","下列关于市政消火栓设置要求的说法，正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","市政消火栓距路边不应大于5．0m",false,{"key":16,"text":17,"correct":14},"B","市政消火栓距路边不宜小于0．2m处",{"key":19,"text":20,"correct":14},"C","市政消火栓距建筑外墙或外墙边缘不宜小于2．0m",{"key":22,"text":23,"correct":24},"D","市政桥桥头和城市交通隧道出入口等市政公用设施处，应设置市政消火栓",true,"根据《消防给水及消火栓系统技术规范》GB50974—20147．2．6，市政消火栓应布置在消防车易于接近的人行道和绿地等地点，且不应妨碍交通，并应符合下列规定：市政消火栓距路边不宜小于0．5m，并不应大于2．0m；市政消火栓距建筑外墙或外墙边缘不宜小于5．0m；市政消火栓应避免设置在机械易撞击的地点，确有困难时，应采取防撞措施，ABC选项错误；根据7．2．4，市政桥桥头和城市交通隧道出入口等市政公用设施处．应设置市政消火栓，D选项正确。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]