[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933679":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933679,604,1,"单选题","某采用高压消防给水系统的高层民用建筑在顶部设有高位消防水池，火灾时补水可靠，该建筑室内消防用水总量为450m3，则该高位消防水池最小有效容积不应小于（ ）m3。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","120",false,{"key":16,"text":17,"correct":14},"B","198",{"key":19,"text":20,"correct":21},"C","225",true,{"key":23,"text":24,"correct":14},"D","328","根据《消防给水及消火栓系统技术规范》GB50974—20144．3．11—4，当高层民用建筑采用高位消防水池供水的高压消防给水系统时，高位消防水池储存室内消防用水量确有困难，但火灾时补水可靠，其总有效容积不应小于室内消防用水量的50％。 本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]