[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933675":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933675,604,1,"单选题","某采用临时高压给消防水系统的建筑设有稳压泵和气压水罐，在对气压水罐调节容积进行计算时，应根据稳压泵启泵次数不大于（ ）次／h计算。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","5",false,{"key":16,"text":17,"correct":14},"B","10",{"key":19,"text":20,"correct":21},"C","15",true,{"key":23,"text":24,"correct":14},"D","20","根据《消防给水及消火栓系统技术规范》GB50974—20145．3．4，设置稳压泵的临时高压消防给水系统应设置防止稳压泵频繁启停的技术措施，当采用气压水罐时，其调节容积应根据稳压泵启泵次数不大于15次／h计算确定，但有效储水容积不宜小于150L。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]