[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933674":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933674,604,1,"单选题","某建筑室内消火栓系统设计流量为45L／s，根据消防水泵接合器流量计算，该建筑的消防水泵接合器数量不应少于（ ）个。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1",false,{"key":16,"text":17,"correct":14},"B","2",{"key":19,"text":20,"correct":21},"C","3",true,{"key":23,"text":24,"correct":14},"D","4","根据《消防给水及消火栓系统技术规范》GB50974—20145．4．3，消防水泵接合器的给水流量宜按每个10L／s～15L／s计算；每种水灭火系统的消防水泵接合器设置的数量应按系统设计流量经计算确定，但当计算数量超过3个时，可根据供水可靠性适当减少．45÷15=3个。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]