[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933673":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933673,604,1,"单选题","墙壁消防水泵接合器的安装高度距地面宜为（ ）m，与墙面上的门、窗、孔、洞的净距离不应小于（ ）m。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","0．70，4．0",false,{"key":16,"text":17,"correct":14},"B","1．10，2．0",{"key":19,"text":20,"correct":21},"C","0．70．2．0",true,{"key":23,"text":24,"correct":14},"D","1．10．4．0","根据《消防给水及消火栓系统技术规范》GB50974—20145．4．8，墙壁消防水泵接合器的安装高度距地面宜为0．70m；与墙面上的门、窗、孔、洞的净距离不应小于2．0m，且不应安装在玻璃幕墙下方；地下消防水泵接合器的安装，应使进水口与井盖底面的距离不大于0．40m，且不应小于井盖的半径。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]