[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933672":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933672,604,1,"单选题","下列有关室内消防给水管道的说法，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","室内消火栓竖管直径应根据竖管最低流量经计算确定，但不应小于DN100",false,{"key":16,"text":17,"correct":18},"B","室内消火栓系统与自动喷水灭火系统合用消防泵时，供水管路应沿水流方向在报警阀后分开设置",true,{"key":20,"text":21,"correct":14},"C","室内消防给水管道每根竖管与供水横干管相接处应设置阀门",{"key":23,"text":24,"correct":14},"D","室内消火栓竖管应保证检修管道时关闭停用的竖管不超过1根，当竖管超过4根时，可关闭不相邻的2根","根据《消防给水及消火栓系统技术规范》GB50974—20148．1．5—3，室内消火栓竖管管径应根据竖管最低流量经计算确定，但不应小于DN100，A选项正确；根据8．1．7，室内消火栓给水管网宜与自动喷水等其他水灭火系统的管网分开设置，当合用消防泵时，供水管路沿水流方向应在报警阀前分开设置，B选项错误；根据8．1．6，室内消火栓竖管应保证检修管道时关闭停用的竖管不超过1根，当竖管超过4根时，可关闭不相邻的2根，CD选项正确。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]