[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933671":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},933671,604,1,"单选题","下列关于室外消防给水管网的说法，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","室外消防给水采用两路消防供水时应布置成环状管网，但当采用一路消防供水时可布置成枝状",true,{"key":16,"text":17,"correct":18},"B","管道的直径应根据流量、流速和压力要求经计算确定，但不应小于DN65",false,{"key":20,"text":21,"correct":18},"C","向环状管网输水的进水管不应少于两条，当其中一条发生故障时，剩余输水干管仅满足生活用水量即可",{"key":23,"text":24,"correct":18},"D","给水管道应采用阀门分成若干独立段，每段室外消火栓的数量不宜超过6个","根据《消防给水及消火栓系统技术规范》GB50974—20148．1．4，室外消防给水管网应符合下列规定：1）室外消防给水采用两路消防供水时应采用环状管网，但当采用一路消防供水时可采用枝状管网；2）管道的直径应根据流量、流速和压力要求经计算确定，但不应小于DN100；3）消防给水管道应采用阀门分成若干独立段，每段内室外消火栓的数量不宜超过5个，A选项正确，BD选项错误；根据8．1．3，向室外、室内环状消防给水管网供水的输水干管不应少于两条，当其中一条发生故障时，其余的输水干管应仍能满足消防给水设计流量，C选项错误。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]