[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933669":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933669,604,1,"单选题","下列关于消防水泵控制柜的说法，正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","消防水泵控制柜应具备自动巡检可调、显示巡检状态和信号等功能，对话界面应有英汉双语介绍，图标应便于识别和操作",false,{"key":16,"text":17,"correct":14},"B","消防水泵控制柜平时应使消防水泵处于手动启泵状态",{"key":19,"text":20,"correct":14},"C","消防水泵控制柜与消防水泵设置在同一空间时，防护等级不应低于IP56",{"key":22,"text":23,"correct":24},"D","消防水泵控制柜设置在专用消防水泵控制室时，防护等级不应低于IP30",true,"根据《消防给水及消火栓系统技术规范》GB50974—201411．0．18，控制柜应具有自动巡检可调、显示巡检状态和信号等功能，且对话界面应有汉语语言，图标应便于识别和操作，A选项错误；根据11．0．1—1，消防水泵控制柜在平时应使消防水泵处于自动启泵状态，B选项错误；根据11．0．9，消防水泵控制柜设置在专用消防水泵控制室时，其防护等级不应低于IP30，与消防水泵设置在同一空间时，其防护等级不应低于IP55，C选项错误，D选项正确。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]