[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933650":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933650,604,1,"单选题","某商业楼，建筑高度为40m，设有室内消火栓系统、自动喷水灭火系统、火灾自动报警系统，则该建筑消防备用电源应满足火灾时消防水泵持续运行（ ）min。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","30",false,{"key":16,"text":17,"correct":14},"B","60",{"key":19,"text":20,"correct":14},"C","120",{"key":22,"text":23,"correct":24},"D","180",true,"根据《消防给水及消火栓系统技术规范》GB50974—2014表3．6．2，高层商业楼的火灾延续时间为3．0h。根据《建筑防火设计规范》GB50016—2014（2018年版）10．1．6，备用消防电源的供电时间和容量，应满足该建筑火灾延续时间内各消防用电设备的要求。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]