[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933648":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933648,604,1,"单选题","下列关于消防设备配电装置的做法，不符合要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","引至消防电梯的两路电源在电梯机房配电箱处切换",false,{"key":16,"text":17,"correct":18},"B","消防水泵的配电线路设置剩余电流保护装置",true,{"key":20,"text":21,"correct":14},"C","防烟风机的配电线路设置短路动作保护装置",{"key":23,"text":24,"correct":14},"D","排烟风机的两路电源在最末一级配电箱切换","根据《建筑防火设计规范》GB50016—2014（2018年版）10．1．8，消防控制室、消防水泵、消防电梯、防烟排烟风机等的供电，要在最末一级配电箱处设置自动切换装置， AD选项正确；消防负荷的配电线路不能设置剩余电流动作保护和过欠电压保护，B选项错误；消防负荷的配电线路所设置的保护电器要具有短路保护功能，但不宜设置过负荷保护装置，如设置只能动作于报警而不能用于切断消防供电，C选项正确。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]