[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933643":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933643,604,2,"多选题","某二级耐火等级的5层大学宿舍，住宿床位数550张，总建筑面积3000m2，建筑内部设置了室内外消火栓系统、自动喷水灭火系统、火灾自动报警系统等，下列关于该场所配置手提式灭火器的方案中，正确的是（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","选用单具灭火级别为3A的灭火器，设计保护距离为10m",true,{"key":16,"text":17,"correct":18},"B","选用单具灭火级别为2A的灭火器，设计保护距离为20m",false,{"key":20,"text":21,"correct":14},"C","选用单具灭火级别为3A的灭火器，设计保护距离为15m",{"key":23,"text":24,"correct":18},"D","选用单具灭火级别为3A的灭火器，设计保护距离为20m",{"key":26,"text":27,"correct":18},"E","选用单具灭火级别为2A的灭火器，设计保护距离为15m","AC","根据《建筑灭火器配置设计规范》GB50140—2005附录D，该建筑灭火器配置场所危险等级属于严重危险级，根据表6．2．1，严重危险级单具灭火器的最低灭火级别应为3A，根据表5．2．1，严重危险级场所单具灭火器的最大保护距离应为15m。本题答案为AC。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]