[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933609":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933609,604,1,"单选题","某工厂的单层总控制室，长度为32m，宽度为12m。配置手提式灭火器，该建筑至少应设（ ）个灭火器配置点。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1",false,{"key":16,"text":17,"correct":18},"B","2",true,{"key":20,"text":21,"correct":14},"C","3",{"key":23,"text":24,"correct":14},"D","4","根据《建筑灭火器配置设计规范》附录C，工厂的总控制室属于严重危险级场所。根据5．2．1，严重危险级场所每具手提式灭火器最大保护距离为15m。该场所长度为32m，因此至少设2个灭火器配置点。以短边6m为直角边，15m为三角形的斜边，另外一条直角边的长度为13.7m；两个点布置在短边中点连线上，布置点之间的间距为4.5m，能够刚好保护室内所有的点。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]