[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933553":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933553,604,1,"单选题","对于100m以上建筑而言，消防应急照明和疏散指示系统的蓄电池的持续应急工作时间不小于（ ）min。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","30",false,{"key":16,"text":17,"correct":14},"B","60",{"key":19,"text":20,"correct":21},"C","90",true,{"key":23,"text":24,"correct":14},"D","180","不同类别建（构）筑物的持续应急时间应符合下列规定: （1）建筑高度大于100m的民用建筑，不应小于1.5 h。 （2）医疗建筑、老年人照料设施、总建筑面积大于100000㎡的公共建筑和总建筑面积大于20000㎡的地下、半地下建筑，不应小于1h。 （3）其他建筑，不应小于0.5h。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]