[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933551":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933551,604,1,"单选题","下列建筑内消防应急照明灯具的照度不符合规定的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","手术部的避难间，不应低于10．0lx",false,{"key":16,"text":17,"correct":18},"B","疏散走道的地面最低水平照度不应低于3．0lx",true,{"key":20,"text":21,"correct":14},"C","人员密集场所内的地面最低水平照度不应低于3．0lx",{"key":23,"text":24,"correct":14},"D","避难走道的地面最低水平照度不应低于5．0lx","根据《建筑设计防火规范》GB 50016-2014（2018年版）中10．3．2，建筑内疏散照明的地面最低水平照度应符合下列规定： 1、对于疏散走道，不应低于1．0lx。 2、对于人员密集场所、避难层（间），不应低于3．0lx；对于老年人照料设施、病房楼或手术部的避难间，不应低于10．0lx。 3、对于楼梯间、前室或合用前室、避难走道，不应低于5．0lx；对于人员密集场所、老年人照料设施、病房楼或手术部内的楼梯间、前室或合用前室、避难走道，不应低于10．0lx。 因此本题选择B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]