[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933536":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933536,604,1,"单选题","机械加压送风系统应采用管道送风，且不应采用土建风道。送风管道应采用不燃材料制作且内壁应光滑。当送风管道内壁为金属时，设计风速不应大于（ ）m／s。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","10",false,{"key":16,"text":17,"correct":14},"B","15",{"key":19,"text":20,"correct":21},"C","20",true,{"key":23,"text":24,"correct":14},"D","25","根据《建筑防烟排烟系统技术标准》（GB51251—2017）第3．3．7条规定，机械加压送风系统应采用管道送风，且不应采用土建风道。送风管道应采用不燃材料制作且内壁应光滑。当送风管道内壁为金属时，设计风速不应大于20m／s，当送风管道内壁为非金属时，设计风速不应大于15m／s； 送风管道的厚度应符合现行国家标准《通风与空调工程施工质量验收规范》GB50243的规定。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]