[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933535":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933535,604,1,"单选题","下列关于排烟量的设计原则的说法错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","排烟系统的设计风量不应小于该系统计算风量的1．2倍",false,{"key":16,"text":17,"correct":14},"B","当采用自然排烟方式时，储烟仓的厚度不应小于空间净高的20％，且不应小于500mm",{"key":19,"text":20,"correct":14},"C","当采用机械排烟方式时，储烟仓的厚度不应小于空间净高的10％，且不应小于500mm",{"key":22,"text":23,"correct":24},"D","中庭周围场所设有排烟系统时，中庭采用机械排烟系统的，中庭排烟量应按周围场所防烟分区中最大排烟量的3倍数值计算，且不应小于107000m3／h",true,"根据《建筑防烟排烟系统技术标准》（GB51251—2017）第4．6．5条规定，中庭周围场所设有排烟系统时，中庭采用机械排烟系统的，中庭排烟量应按周围场所防烟分区中最大排烟量的2倍数值计算，且不应小于107000m3／h；中庭采用自然排烟系统时，应按上述排烟量和自然排烟窗口处风速不大于0．5m／s计算有效开窗面积。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]