[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933534":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933534,604,1,"单选题","根据《建筑设计防火规范》GB 50016-2014（2018年版）的要求，下列生产建筑中，可不设置排烟设施的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","建筑面积为5100m2的空调组装车间",false,{"key":16,"text":17,"correct":14},"B","建筑面积为1000m2的造纸厂备料车间",{"key":19,"text":20,"correct":14},"C","占地面积为1200m2的天然橡胶仓库",{"key":22,"text":23,"correct":24},"D","单层服装加工厂房内长度为31m的疏散走道",true,"《建筑设计防火规范》GB 50016-2014（2018年版），8.5.2，厂房或仓库的下列场所或部位应设置排烟设施：1、人员或可燃物较多的丙类生产场所，丙类厂房内建筑面积大于300m2且经常有人停留或可燃物较多的地上房间；2、建筑面积大于5000m2的丁类生产车间；3、占地面积大于1000m2的丙类仓库；4、高度大于32m的高层厂房（仓库）内长度大于20m的疏散走道，其他厂房（仓库）内长度大于40m的疏散走道。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]