[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933533":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933533,604,1,"单选题","机械加压送风系统计算送风量时，采用常开风口，关于设计层数内疏散门开启数量的说法错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","对楼梯间而言，当地上楼梯间为15层以下时，设计两层内的疏散门开启，取N=2",false,{"key":16,"text":17,"correct":18},"B","对楼梯间而言，当地上楼梯间为15层及以上时，设计两层内的疏散门开启，取N=2",true,{"key":20,"text":21,"correct":14},"C","对楼梯间而言，当为地下楼梯间时，设计一层内的疏散门开启，取N=1",{"key":23,"text":24,"correct":14},"D","对前室、合用前室而言，当防火分区跨越楼层时，设计跨越楼层内的疏散门开启，取N=跨越楼层数，最大值为3","当地上楼梯间为15层及以上时，设计三层内的疏散门开启，取N=3。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]