[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933523":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933523,604,1,"单选题","下列关于机械加压送风系统组件设置要求的说法中，不正确的是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","前室应每层设一个常闭式加压送风口，并应设手动开启装置",false,{"key":16,"text":17,"correct":14},"B","送风机的进风口与排烟风机的出风口应分开布置，且竖向布置时，送风机的进风口应设置在排烟出口的下方",{"key":19,"text":20,"correct":14},"C","机械加压送风机宜采用轴流风机或中、低压离心风机",{"key":22,"text":23,"correct":24},"D","送风机的进风口宜设在机械加压送风系统的上部",true,"根据《建筑防烟排烟系统技术标准》GB51251—20173．3．6—2，前室应每层设一个常闭式加压送风口，并应设手动开启装置，A选项正确；根据3．3．5—3，送风机的进风口不应与排烟风机的出风口设在同一面上。当确有困难时，送风机的进风口与排烟风机的出风口应分开布置，竖向布置时，送风机的进风口应设置在排烟出口的下方，其两者边缘最小垂直距离不应小于6．0m，水平布置时，两者边缘最小水平距离不应小于20．0m，B选项正确；根据3．3．5，机械加压送风风机宜采用轴流风机或中、低压离心风机，C选项正确；根据3．3．5—2，送风机的进风口宜设在机械加压送风系统的下部，D选项错误。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]