[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933520":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},933520,604,1,"单选题","下列关于排烟风机的说法错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","排烟风机应设置在专用机房内，不能与其他风机合用机房",true,{"key":16,"text":17,"correct":18},"B","排烟风机入口处应设置280℃能自动关闭的排烟防火阀",false,{"key":20,"text":21,"correct":18},"C","排烟风机房间应采用耐火极限不低于2．00h的隔墙和1．50h的楼板及甲级防火门与其他部位隔开",{"key":23,"text":24,"correct":18},"D","排烟风机与排烟管道上不宜设有软接管","排烟风机应设置在专用机房内，当必须与其他风机合用机房时，应符合下列条件：①机房内应设有自动喷水灭火系统。②机房内不得设有用于机械加压送风的风机与管道。③排烟风机与排烟管道上不宜设有软接管。当排烟风机及系统中设置有软接头时，该软接头应能在280℃的环境条件下连续工作不少于30min。当风机设置于专用机房内时，风机控制柜应放置在专用机房内，当风机设置于室外时，风机控制柜应放置在附近公共部位，并应采取防护措施。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]