[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933519":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933519,604,1,"单选题","下列关于排烟量的选取说法错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","当一个排烟系统担负多个防烟分区（具有相同净高）排烟时，对于建筑空间净高大于6m的场所，其排烟量应按最大一个防烟分区的排烟量计算",false,{"key":16,"text":17,"correct":18},"B","建筑空间净高≤6m的场所，其机械排烟量应按不小于60m3／（hm2）计算，且取值不应小于13000m3／h",true,{"key":20,"text":21,"correct":14},"C","当公共建筑中庭周围场所设有机械排烟时，中庭的排烟量可按周围场所中最大排烟量的2倍数值计算，且不应小于107000m3／h",{"key":23,"text":24,"correct":14},"D","当公共建筑室内与走道或回廊均需设置排烟系统时，其走道或回廊的机械排烟量可按60m3／（hm2）计算，且不应小于13000m3／h，或设置不小于走道、回廊建筑面积2％的排烟窗","建筑空间净高≤6m的场所，其机械排烟量应按不小于60m3／（hm2）计算，且取值不应小于15000m3／h。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]