[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933518":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933518,604,1,"单选题","下列关于补风系统的说法中，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","设置排烟系统的场所都应设置补风系统",false,{"key":16,"text":17,"correct":18},"B","补风系统应直接从室外引入空气，且补风量不应小于排烟量的50％",true,{"key":20,"text":21,"correct":14},"C","补风口与排烟口分别设置在同一空间内相邻的防烟分区时，补风口与排烟口水平距离不应少于5m",{"key":23,"text":24,"correct":14},"D","自然补风口的风速不宜大于5m／s","根据《建筑防烟排烟系统技术标准》GB51251—20174．5．1，除地上建筑的走道或建筑面积小于500m2的房间外，设置排烟系统的场所应设置补风系统，A选项错误；根据4．5．2，补风系统应直接从室外引入空气，且补风量不应小于排烟量的50％，B选项正确；根据4．5．4，补风口与排烟口设置在同一空间内相邻的防烟分区时，补风口位置不限：当补风口与排烟口设置在同一防烟分区时，补风口应设在储烟仓下沿以下；补风口与排烟口水平距离不应少于5m，C选项错误；根据4．5．6，机械补风口的风速不宜大于10m／s，人员密集场所补风口的风速不宜大于5m／s，自然补风口的风速不宜大于3m／s．D选项错误。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]